Effective Temperature Process Control
Single-Loop PID Temperature Process Controllers
Temperature process controllers offers easy to use, accurate, reliable PID control. These single loop panel mount controls include auto-tuning, a universal sensor input and PID control output. Available in standard 1/4 DIN size, these auto-tuning temperature controllers automatically set PID control parameters for optimal system performance. Manual settings also permit on-off, P, PI or PID control modes.
- User-defined menu system allows the user to assign up to 20 paramaters in the operations menu.
- Dual display provides better recognition of process changes, including current process value and set value.
- Ramp to set point feature controls temperature rise.
- Includes a single alarm output as standard.
Dimensions
|
DIN Size
|
Behind Panel (max.)
|
Width
|
Height
|
|
¼ DIN
|
101.1 mm (3.98")
|
99.8 mm (3.93")
|
99.8 mm (3.93")
|
Specifications
Line Voltage/Power
- 100 to 240V-(ac), ±10/-15 percent; (85-264V~[ac] 50/60Hz, ±5 percent
- 24V=(ac/dc), ±10/-15 percent; 50/60Hz., ±5 percent
- 10VA maximum power consumption
- Data retention upon power failure via nonvolatile memory
Environment
- -18 to 65°C (0 to 149°F) operating temperature
- -40 to 85°C (-40 to 185°F) storage temperature
- 0 to 90 percent RH, non-condensing
Accuracy
- Calibration accuracy and sensor conformity: ±0.1 percent of span, ±1°C @ the calibrated ambient temperature and rated line voltage
- Calibrated ambient temperature = 25°C ± 3°C (77°F ±5°F)
- Accuracy span: 540°C (1000°F) minimum
- Temperature stability: ±0.1°C/°C (±0.2°F/°F) rise in ambient maximum
Agency Approvals
- UL 3121, C-UL, CSA, CE, IP65/NEMA 4Xand NSF-2
- Limit version features FM approval
Controller
- Microprocessor based user-selectable control modes
- Single universal input, up to three outputs
- Control sampling rates: input = 6.5Hz, display = 10Hz, outputs = 6.5Hz
Operator Interface
- Dual 4 digit, 7 segment LED displays
- Advance, infinity and up down keys
- IrDA infrared port (not available on 1/22 DIN)
- Isolated EIA 485 Modbus&tm; serial communications
Wiring Termination - Touch Safe Terminals
- Input power and control outputs 12 to 22 AWG
- Sensor inputs and proces outputs 20 to 28 AWG
Universal Input
- Thermocouple, grounded or ungrounded sensors
- RTD 2- or 3-wire, platinum, 100Ω @ 0°C calibration to DIN curve (0.00385 Ω/Ω/°C)
- Process, 0-20mA @ 1Ω or 0-10V=(dc) @ 20koemga input impedance; Scalable
- 0-50mV
- Inverse scaling
- >20MΩ input impedance
- Maximum of 20Ω source resistance